Triple Dealkalizer System Being Prepared for Shipment |
What a dealkalizer does:
| A dealkalizer removes Alkalinity which breaks down in the boiler and generates CO2 and carbonic acid (H2CO3) in the condensate. The removing of CO2 and Carbonic acid reduces corrosion rates within the condensate piping |
---|---|
Inlet alkalinity:
| Average inlet M-Alkalinity- 40 ppm- 50 ppm |
Savings the customer wants to achieve:
| • Reduced Corrosion of steam condensate return piping • Lower return condensate iron levels in boiler feedwater and cleaner boiler tube surfaces • Lower Operating expenses on fuel with cleaner boiler tubes • Eliminating alkalinity via the dealkalizer allows for higher boiler cycles of concentration and lower fuel costs |
Flow Operating Conditions:
| Typical: 140 gpm typical Peak: 200 gpm Minimum: 40 gpm |
System Configuration:
| • Triple 42 " diameter X 72" ASME Code fiberglass tanks • Each tank has a front mounted/supported Pentair Fleck 3900 valve with NXT controller • All Interconnecting pipe is Schedule 80 PVC piping • Each tank is individually skid mounted |
Control Valves:
| Multi-Port Fleck 3900 valves side mounted and supported via welded steel frame |
System Operation:
| Progressive Flow and Demand Flow operations |
Added Features:
| Contacts on the Fleck valve indicate to the DCS that the unit is in operation, standby, or regeneration |
Additional Information:
Technical bulletin for Res-Kem's dealkalizer equipment