| 770MAX and M300 Thornton Meters Installed in a Customer's Water Treatment Plant |
Our calibration service coverage area is the mid-Atlantic and New England States.
For Additional Information:
Contact us for calibration service estimate
![]() |
| 770MAX and M300 Thornton Meters Installed in a Customer's Water Treatment Plant |
| New Assembly and Warehousing Space in the Aston Facility |
| Multi-Media Filter and Carbon Filter with Media Ready for Shipment |
| What the company does | Coal fired electric generation plant |
| Water treatment application |
Backwashable Multi-media filter
Backwashable Activated carbon filter This water enters a previously provided Res-Kem softener which pretreats the water before entering the RO system |
| Operating conditions, e.g. flow, temp, continuous, etc. |
The systems treat the plant’s well water.
Inlet temperature approximately 55 F Flow rate 40 gpm |
| System configuration, e.g. # of tanks, standby units, etc. | Single, 48” ASME code 100 psig, tank multi-media filter Single, 48” ASME code 100 psig, activated carbon filter |
| Materials of construction of tanks, piping, valves, frame, media, etc. | Threaded carbon steel face piping PVC hub and laterals Res-Karb CS1240 activated carbon |
| Type of valves and actuators | Cast iron, Series 42, Aquamatic diaphragm valves |
| Control philosophy | Time clock backwashed multi-media filter using Aquamatic NXT stager/controller Time clock backwashed activated carbon filter Aquamatic NXT stager/controller |
![]() |
| Dual, Skid Mounted Stainless Steel Condensate Polisher with Headers |
Customer
|
An independent energy development company specializing in the development, engineering, construction, start up, commissioning, operation, maintenance and management, as well as, ownership of Central Energy Centers, Renewable Energy projects and Combined Heat, Chilling and Power Production Facilities.
|
General water treatment application
|
Two large 48”X60” sodium cycle condensate polisher for removal of contaminants in the return condensate and the return condensate from the steam driven chillers on-site
|
Savings and/or ROI the customer wants to achieve
|
Fuel and chemical saving related to the removal of iron and calcium from the condensate streams and ultimately the boiler feedwater
|
Operating conditions
|
250 gpm max, 150 gpm continuous operating at 180F
|
System configuration
|
Twin parallel / Alternating system
|
Materials of construction
|
Skid mounted
304 SS pressure vessels
Schedule 10 welded /flanged face piping
|
Type of valves and actuators
|
Bray valves with Bray actuators
|
System Control
|
Allen Bradley PLC operates the system as alternating or parallel
|
System schematic
|
Polisher collectively handles two condensate streams – return condensate from campus and condensate from steam driven chillers
|
Special Features
|
Sample cooler mounted on skid which can sample the inlet and outlet of each vessel
Inlet and outlet headers between each system on skid
|
| Confined Space Entry Training Hands-on LOTO (Lock-Out Tag-Out) Training |
| Hot Water Softener with Stainless Steel Piping and Bray Butterfly Valves |
Operating Temperature
|
140F water for laundry
|
System Configuration
|
Single hot water softener with automatic bypass
|
Materials of Construction
|
Carbon steel tank, non-code
304L stainless steel face piping
304L stainless steel internals
Cast iron Bray lug valves with 316 butterfly discs
|
Piping Connections
|
Welded
|
Valves and Actuators
|
Bray Butterfly Series 31 valves with Series 93 Air to Open/Spring Return actuators
|
Control Scheme
|
Single, time clock initiated regeneration with automatic hard water bypass
|
![]() |
| 304L Stainless Steel Hub and Lateral Bottom Distributor |
![]() |
| Topographical Map of Pennsylvania Showing Rock Formations |
![]() |
| Res-Kem Dual Tank Condensate Polishers Designed to Treat a Maximum of 300 gpm |
| What is the Res-Kem water treatment application? | Sodium cycle condensate polishing to remove iron and hardness |
| What are the operating conditions? | Flow: Maximum of 150 gpm/vessel Pressure: 30-100 psi Temperature: Maximum of 200F Continuous |
| What is the system configuration? | Dual tank, parallel operation 30” in diameter tanks |
| What ion exchange resin was used? | 15 cubic feet of Purolite C-150 highly cross-linked macroporous cation exchange resin in each tank |
| Materials of construction? | 304 SS ASME code with a 100 psig design pressure 304 SS Hub and Lateral Galvanized Schedule 40 Flanged and Threaded Face Piping |
| Type of Valves? | AquaMatic High Temperature diaphragm valves |
![]() |
| Res-Kem's New Regional Service Center in Raynham, MA |